Setting a Lutron SeeTouch QS Keypad for scene control

The scene settings are programmed on the Grafik Eye QS unit, this guide will explain how to ensure that the keypad is accessing your chosen scenes. Unprogrammed (out of the box) SeeTouch Keypads and Grafik Eye QS units will work together until they are reprogrammed otherwise.

In order for keypads to communicate with a control unit, each keypads must be individually configured to “talk” to a “listening” control unit. Only one keypad can be in set-up mode at a time.

Step 1: Entering Setup Mode

Press and hold simultaneously for 3 seconds the top and bottom buttons (not including raise/lower buttons) on the keypad. When the LED indicator lights on each button start to sequence, the keypad is in setup mode.

Press the top and bottom buttons

If your keypad has more than one column of buttons, you will program each set as if each were its own keypad.

Multi Column SeeTouch Keypad

Step 2: Select keypad function (optional)

The info screen on the Grafik Eye QS control unit will display a prompt to change your keypad’s function (type). For this guide you should ensure that your keypad is set to one of the scene options (see the table below).

Grafik Eye Display

   2 Button 3 Button 5 Button Raise/Lower 8 Button Raise/Lower 10 Button Raise/Lower
Left Right Left Right
Scene Options

1, Off

5, Off

9, Off

13, Off

1, 2

5, 6

9, 10

13, 14

1, 2, Off

5, 6, Off

9, 10, Off

13, 14, Off

1-3

5-7

9-11

13-15

1-4, Off

5-8, Off

9-12, Off

13-16, Off

1-5

5-9

9-13

1, 2, Off

5, 6, Off

9, 10, Off

13, 14, Off

1-3

5-7

9-11

13-15

1, 2, Off

5, 6, Off

9, 10, Off

13, 14, Off

1-3

5-7

9-11

13-15

1, 2, Off

5, 6, Off

9, 10, Off

13, 14, Off

1-3

5-7

9-11

13-15

1, 2, Off

5, 6, Off

9, 10, Off

13, 14, Off

1-3

5-7

9-11

13-15

Press the OK button on the Grafik Eye QS control unit to display the current keypad function/type. To change, use the master buttons to scroll through the available choices until the function that you want displays on the info screen.

Grafik Eye Keypad Type

The menu will only display the functions that are available for the keypad model that’s “talking” to it. The example above is for a 5-button SeeTouch QS with Raise/Lower buttons. Press the OK button to accept and save your highlighted choice.

Step 3: Programming the keypad

Press and hold the top button on the Grafik Eye QS control unit lighting column until its LEDs flash in unison. Repeat for each Grafik Eye QS control unit you want to “listen” to the keypad for the selected function.

 Grafik Eye Keypad Programming

 If you want to maintain communication between your chosen keypad and the Grafik Eye control unit DO NOT follow the next step. To stop a control unit from “listening” to a keypad, put the keypad in setup mode, and press and hold (for 3 seconds) the bottom button on the lighting keypad  of the Grafik Eye QS unit that you want to stop “listening”.

Unlinking a Grafik Eye and Keypad

Step 4: Exit Setup Mode

Press and hold the top and bottom buttons on the SeeTouch QS keypad simultaneously for 3 seconds. The LEDs will return to normal.

Exit SeeTouch QS Setuo Mode